Remote Zero Speed Switch, ZS10F |
|

|

The following examples of
ZS10F Zero Speed Switch Systems Consist of:
ZS10F Zero Speed Switch System
Utilizing Axial Magnetic Target Disk
ZS10F Zero Speed Switch System
Utilizing Radial Magnetic Target Disk
ZS10F Zero Speed Switch System
Utilizing Geartooth Wheel
Indicators and Terminal Block
|
Features and Benefits
- Sensor interface for over speed, under speed and zero speed measurement
- Easy interface to existing systems
- Interfaces variety of sensor types
- Frequency input
- Plug-n-play units with factory programmed parameters
- Operating voltages: 12, 24 VDC and 120, 240 VAC
- Isolated outputs
- Diagnostic indicators
- Prompt alert for stalled or zero speed condition
- Helps prevent equipment damage and material spoilage
- DIN rail mount
Overview
The ZS10F Remote Zero Speed Switch is used in applications where a sensor is already in use,
but the sensor cannot measure over speed, under speed or zero speed conditions. Use the ZS10F Remote Zero Speed Switch as an interface between sensor and control circuitry to enable over speed, under speed and zero speed measurement.
The ZS10F is particularly useful in applications where environmental conditions (such as high temperature) prohibit the use of certain
electronics. In the case of high temperature, the sensor is installed in the prohibitive area and wired to the ZS10F Remote Zero
Speed Switch which is located a safe distance from the high temperature zone.
For high temperature sensors, see our Digital Output Hall Effect Sensors.
Detail
The ZS10F Remote Zero Speed Switch is a plug-n-play device with factory programmed parameters and is DIN rail mountable, making
installation easy. It can be integrated with existing industrial control systems or used as a stand-alone unit.
The ZS10F uses frequency input from various types of sensors to determine the presence of motion or the lack thereof. When motion is
either detected or reaches setpoint, the relay output changes state. It remains in this state until either under speed or zero speed
condition occurs, depending upon application.
The ZS10F Remote Zero Speed Switch Module supplies 12 VDC to external sensor.
Sensor types used with the ZS10F:
Specifications
Power Requirements
12 VDC, 50/60 Hz (for Part No.ZS10F-12)
24 VDC, 50/60 Hz (for Part No.ZS10F-24)
120 VAC, 50/60 Hz (for Part No. ZS10F-120)
240 VAC, 50/60 Hz (for Part No. ZS10F-240)
Current Draw
68 mA
Circuit Protection
External ½ amp fuse required
Input Signal
12VDC, 3 wire, sinking (NPN)
Relay
- Output:
SPDT Form 'C' dry relay contact(N.O/N.C.)
- Contact Rating:
5 A at 120 VAC; 5 A at 30 VDC
- Maximum switching frequency:
1,800 operations/hr (under rated load)
- Life expectancy:
Mechanical 10,000,000 operations min. (at 1,800 operations/hr)
Electrical 100,000 operations min. (at 1,800 operations/hr)
See the Ordering Information table for part numbers and corresponding specifications.
Related Links
|
|
| Part Number |
Description |
Input Voltage |
Input Signal |
Contact Rating |
Relay Output |
Load Type |
Speed Switch Type |
Setpoint |
Target |
| ZS10F-12 |
Remote Zero Speed Switch, DIN rail mount |
12 VDC |
12 VDC,
3 wire,
sinking signal (NPN) |
5 A @ 250 VAC |
N.O./N.C. |
Control Circuit
or
Logic Input |
External Sensor Required |
Fixed Setpoint |
Depends on external sensor used, such as, photoeye, hall effect, capacitive, inductive, encoder, etc. |
| ZS10F-24 |
Remote Zero Speed Switch, DIN rail mount |
24 VDC |
12 VDC,
3 wire,
sinking signal (NPN) |
5 A @ 250 VAC |
N.O./N.C. |
Control Circuit
or
Logic Input |
External Sensor Required |
Fixed Setpoint |
Depends on external sensor used, such as, photoeye, hall effect, capacitive, inductive, encoder, etc. |
| ZS10F-120 |
Remote Zero Speed Switch, DIN rail mount |
120 VAC |
12 VDC,
3 wire,
sinking signal (NPN) |
5 A @ 250 VAC |
N.O./N.C. |
Control Circuit
or
Logic Input |
External Sensor Required |
Fixed Setpoint |
Depends on external sensor used, such as, photoeye, hall effect, capacitive, inductive, encoder, etc. |
| ZS10F-240 |
Remote Zero Speed Switch, DIN rail mount |
240 VAC |
12 VDC,
3 wire,
sinking signal (NPN) |
5 A @ 250 VAC |
N.O./N.C. |
Control Circuit
or
Logic Input |
External Sensor Required |
Fixed Setpoint |
Depends on external sensor used, such as, photoeye, hall effect, capacitive, inductive, encoder, etc. |